Enviro Quick Step Installation Manual

Enviro Quick Step Installation Manual PDF »

 

Firebox dimensions

easy install modern enviro gas fireplace unit dimensions image

easy install modern enviro gas fireplace

1 – Electrical power cable (Requires isolation switch)
2 – Incoming gas connection (1/2” BSP Male connector)
3 – Extraction fan
4 – Incoming air

Gas imput
High 44 MJ/h Low 23 MJ/h

easy install modern enviro gas fireplace air vent image

A – Fascia attaches to the front of the firebox to finish flush with the wall
B – Your choice of pebbles, coals or logs placed into the firebox. Do not obscure the gas outlets
* C and D are only applicable if installing under bench top and or into Joinery.
C – Minimum enclosure height from top of box = 300mm
D – 1 Inlet and 1 outlet ventilation with a cross sectional area of 5000mm for each.

Minimum framing dimensions

easy install modern enviro gas fireplace

* Note: Standard Fascia finishes flush with the bottom of the firebox so ensure a neat finish to plaster/gyprock.

Choice of firebox height

With it’s revolutionary design, the Enviro can be mounted at any height on the wall. You can choose to install the
Enviro at ground level with standard fascia or further up the wall with extended fascia.

easy install modern enviro gas fireplace hearth image

Resting on the heath
Standard fascia
If mounting the Enviro at floor level, it is recommended that a non combustible hearth be used for a minimum 350mm in front of the fire.

easy install modern enviro gas fireplace

Further up the wall
Extended facsia

Option of moving the gas inlet

To fit in with you space, the Enviro has an option to move the gas inlet from the back to the side of the heater.

enviro side view

Step 1– Remove round flange on bottom left side. Identify the removable panel on the left side of the heater. Unscrew the 4 screws and remove panel.

easy install modern enviro gas fireplace

Step 2 – Using two spanners, undo the gas pipe from the main connection.

easy install modern enviro gas fireplace gas connection

Step 3 – Remove flexible pipe from the heater.

easy install modern enviro gas fireplace

Step 4 – Straighten flexible pipe using fingers as shown.

easy install modern enviro gas fireplace connection

Step 5 – Put flexible pipe back through hole (S3) and reconnect the pipe (S2) then replace side panel (S1). Finally, replace the little round flange from the side and screw into place to cover the hole on the back panel.

Attaching the fascia

While attaching the facsia is straight forward, it is important that it remains vertical all the time to make sure the top and bottom clip in by way of clips at both the top and bottom. (Before fascia can be removed, door must be unscrewed and removed)

easy install modern enviro gas fireplace door image
easy install modern enviro gas fireplace fascia image
easy install modern enviro gas fireplace
easy install modern enviro gas fireplace fascia

 

Minimum clearances required for balanced flue terminals or the flue terminals of outdoor appliances

(according to AS5601-2004[AGA gas installation code] or NZS 5261 [New Zealand]

easy install modern enviro gas fireplace cowl clearances

a – Bellow eaves, balconies or other projections 300 mm

b – From the ground or above a balcony 300 mm

c – From a return wall or external corner 500 mm

d – From a gas meter (M) 1000 mm

e – From an electricaity meter or fuse box (P) 500 mm

f – From a drain or soil pipe 150 mm

g – Horizontal from an building structure 500 mm

h – From any other flue terminal, cowl or combustion air intake 500 mm

j – Horizontally from an openable window, door, or non-mechanical air inlet, or any other opening into a building, with the exception of sub-floor ventilations 500 mm

k –Vertically below an openable widow, door,or non-mechanical air inlet, or any other opening into a building, with the exception of sub-floor ventilation 150 mm

l – Minimum horizontal clearance to any surface (such as an exterior wall) for vertical terminations 610 mm
m Minimum height above roof line for vertical termination 600 mm

Using your flexible flue pipe

The Enviro’s revolutionary flue system incorporates one 65mm diameter pipe and one 58mm diameter pipe.

Heatmaster Seamless flexible Flue   Use 3 bends only

Our flexible flue has the ability to bend 3 times between the heating unit and the cowl. This includes the bend straight out of the heater if you’re fluing through the ceiling or floor.

     
Heatmaster Seamless flexible flue   Make the flue pipe go over the bearers and joists

You may bend the flue over joists and bearers. It is recommended that a 20mm clearance be maintained between the smaller gas exhaust flue and combustible materials.

     
Heatmaster Seamless flexible Flue   Fluing where the pipe had a spot lower than the rest

Never allow a low spot in the flue. Installing the flue with a dip or “goose neck” can result in reduced efficiency or even prevent the fire from working.

 

Configure triangle

Using up to three bends, use this triangle to work out measurements for your 4.5 mtr flue. Remember, the first bend out of the Heater is counted as one. The Enviro can be flued through the roof, wall or floor. *See your Heatmaster dealer for full details.

easy install modern enviro gas fireplace

 

Key Information – Quick step check list

Plumber

  • Incoming gas connection provided – 1/2 inch BSP male connector
  • Gas input – 44MJ high
    23MJ low
  • Manifold pressure
    High (Nat gas) 0.69 Kpa
    Low (Nat gas) 0.22 Kpa
    High (LPG) 2.25 KPA
    Low (LPG) 0.63 KPA
    Manifold pressure is factory set.

Electrician

Standard flex 2m, 3 pin plug provided. Requires power point with double pole isolation switch.

Addition literature

Supplements for flue installation and heat transfer can be obtained by contacting your Heatmaster dealer.

*All information contained in this mini summary is correct at the time of publication. This is only a summary and should be read in conjunction with the full installation instructions. Pictures are representative only and are not drawn to scale. Installation should be carried out by a licensed gas fitter and any electrical work carried out by a licensed electrician.

 